SP Powerworld ADVR-2100M is a direct replacement for the Original Marathon DVR2000 Series.
£200.00 plus VAT
Accepted worldwide as the only Quality and Legal aftermarket replacement. It's been designed to work in exactly the same way and operates at the same performance. It’s the same size, function and has the same wiring connections, it also comes with 12 months warranty.
Ex stock - shipped Worldwide. For EURO or USD pricing please contact us:
Office: info@sp-powerworld.com
Tel: +44 (0)115 923 2568 (United Kingdom)
Tel: (24-hour) +44 (0)7484709956 (United Kingdom)
*All manufacturer names, numbers, symbols and descriptions are used for reference purpose only and do not imply that any part is the product of these manufacturers.
Features:
- Power input single phase 60 to 300 Vac @ 50 to 500 Hz
- Sensing input 1 or 3 phase 220 to 600 Vac programmable
- Voltage regulation less than +/-0.5%
- 50/60 Hz selectable
- Multiple power input source SHUNT, AUX, HARMONIC, PMG
- Inverse-time over excitation and under frequency protection
- Soft start voltage ramping
- Built-in high capacity protection fuse
- Panel mounted, internal wiring external adjustment
|
Specifications:
Sensing Input |
- Voltage 220 to 600 Vac 1 phase or 3 phase DIP switch setting
- Frequency 50/60 Hz DIP switch setting
|
Power Input |
- Voltage 60 to 300 Vac 1 phase 2 wire
- Frequency 50 to 500 Hz
|
Excitation Output |
- Voltage Continuous 125 Vdc @ power input 220 Vac
- Current Continuous 5A Intermittent 7A for 10 seconds
- Resistance ≧ 13 ohms @ power input 110 Vac / ≧ 25 ohms @ power input 220 Vac
|
External Voltage Adjustment |
- Max. +/-5% @ 500 ohms 1 watt potentiometer
- Max. +/-10% @ 1K ohms 1 watt potentiometer
|
Voltage Regulation |
- Less than +/-0.5% (with 4% engine governing)
|
Build Up Voltage |
- 5Vac 25Hz residual volts at power input terminal
|
Soft Start Ramp Time |
|
EMI Suppression |
- Internal electromagnetic interference filtering
|
Static Power Dissipation |
|
Burden in Shunt & PMG Wiring |
- 550 VA @ power input 110 Vac
- 1100 VA @ power input 220 Vac
|
Quadrature Droop Input |
- CT 1A or 5A greater than 5VA (DIP switch setting)
- Sensitivity Max. +/-7% @ P.F +/-0.7
|
Analogue Input |
- Input resistance greater than 2K ohms
- Max. Input +/-5 Vdc or +10 Vdc
- Sensitivity 1 Vdc for 2.5% Generator Volts
|
Under Frequency Protection(Factory Presets) |
- 50 Hz system knee point at 45 Hz
- 60 Hz system knee point at 55 Hz
|
Over Excitation Protection |
- Inverse-time 125 +/-4 Vdc @ power input 220 Vac
|
Voltage Thermal Drift |
- Less than 3% at -40 to +70 °C
|
AVR Control Functions
|
VOLT |
|
STAB |
|
U/F |
- Setting under frequency protection knee point
|
DROOP |
|
TRIM |
- Analogue input adjustment
|
DIP |
- Voltage droop ratio setting
|
Indication LED
|
O/E |
- Over excitation protection indicator
|
U/F |
- Under frequency protection indicator
|
Environment
|
Operating Temperature |
|
Storage Temperature |
|
Relative Humidity |
|
Vibration |
|
Optional Accessories
|